Flammable-filled transformers in underground construction
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
July 16, 2008
Letter # 20070626-7800
Re: Oil-filled transformers and underground construction
Question: Do all filled transformers, including transformers filled with non or less flammable dielectrics, used in underground construction have to comply with the requirements of 29 CFR 1926.800(s)(3)?
Answer: Filled transformers being used in underground construction must comply with 29 CFR 1926.800(s)(3) if the material that they are filled with is in any way flammable. 29 CFR 1926.800(s)(3) states:
Oil-filled transformers shall not be used underground unless they are located in a fire-resistant enclosure suitably vented to the outside and surrounded by a dike to retain the contents of the transformers in the event of rupture.
The hazard associated with 29 CFR 1926.800(s)(3) is a fire hazard. In order to protect against fire hazards in underground construction, employers utilizing transformers filled with flammable material must adhere to the requirements of the standard. The standard requires using a fire-resistant enclosure to cover the transformer, suitably venting the enclosure to the outside, and surrounding the enclosure by a dike. Accordingly, any underground transformer filled with a material that is flammable in any way must comply with 29 CFR 1926.800(s)(3).
Noah Connell, Acting Director
Directorate of Construction
What does federal law require in your situation?
Ezel checks current federal labor law against your facts and answers with citations.
Opens in Ezel Pro.
- Checks the law as it stands today, not only this page
- Cites every source it relies on, so you can verify it
- Chat, drafting and research in one workspace