Summary An electrical contractor asked about OSHA's earlier statement that temporary cable supports could be no farther than 4.5 feet apart. OSHA said the earlier letter had addressed a different question and that changes to electrical standards prompted review, so it would strike that sentence and issue a new interpretation. OSHA later addressed support spacing in a May 13, 2004 letter; this April letter is now archived as historical guidance.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
2004-04-05
Date issued
April 5, 2004
Status
Archived by the agency
OSHA labels the letter an archive document that may no longer represent policy. It announced withdrawal of an earlier support-spacing sentence while OSHA reviewed the issue; OSHA later addressed support spacing in its May 13, 2004 letter.
Status last verified October 8, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

The current status of this document is unclear
OSHA labels the letter an archive document that may no longer represent policy. It announced withdrawal of an earlier support-spacing sentence while OSHA reviewed the issue; OSHA later addressed support spacing in its May 13, 2004 letter. It may no longer reflect the agency's current position. Treat this page as historical context, not current guidance, and verify current law before relying on anything here.
About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

April 5, 2004

Mr. Kent Davis

ARC Electric, Inc.

[Recipient address omitted]

Re: Minimum distance between supports for temporary wiring; §1926.405.

Dear Mr. Davis:

This is in response to your letter of March 24, 2004, to the Occupational Safety and Health Administration (OSHA) concerning §1926.405 "Wiring Methods, components, and equipment for general use."

You call our attention to a statement we made in our October 4, 2000, letter to Ms. DesRosier. That letter refers to a minimum distance between supports that secure temporary cable; specifically, we stated, "Cable shall be secured in place at intervals not exceeding 4½ feet and within 12 inches from every cabinet, box or fitting."

It has come to our attention that Ms. DesRosier was not inquiring about the minimum interval at which temporary cable should be secured; rather, she sought clarification about the propriety of using Romex-style (nonmetallic-sheathed) cable. Further, changes to the National Electric Codebook (NEC) have resulted in a need for us to reexamine the question of minimum securing distances for temporary cables.

In light of this information, we will modify our response to Ms. DesRosier by striking out the above-quoted sentence. We are now in the process of reviewing the issue and will issue an interpretation on it as soon as the review is complete.

If you need additional information, please contact us by fax (202-693-1689) at: U.S. Department of Labor, OSHA, Office of Construction Standards and Guidance. You can also contact us by mail at U.S. Department of Labor, OSHA, Office of Construction Standards and Guidance, Room N3468, 200 Constitution Avenue, N.W., Washington, D.C. 20210, although there will be a delay in our receiving correspondence by mail.

Sincerely,

Russell B. Swanson, Director

Directorate of Construction