Corrected Tables A and B for 1926 Subpart R, the Steel Erection Standard.
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
December 19, 2002
R. Donald Murphy
Managing Director
Steel Joist Institute
[Recipient address omitted]
Re: Errors in Tables A & B of 29 CFR Part 1926 Subpart R (steel erection standard)
Dear Mr. Murphy:
This is in response to your letter of October 4, 2002, in which you ask that OSHA make several corrections to erection bridging Tables A and B in the new steel erection standard (29 CFR Part 1926 Subpart R). You note that in several instances the Tables erroneously indicate that certain joists require erection bridging. You also point out that the definition of the abbreviation "NM" is incorrect.
Response: We agree that there are several errors in Tables A and B. The Tables were originally designed for the proposed rule, which required bridging on all joists over 40 feet long. However, the final rule differs from the proposed rule in that only certain joists over 40 feet are required to have erection bridging. Errors were made in adjusting the Tables for the final rule; some spans in the tables were incorrectly identified and the note under the tables was not revised. There are also two typographical errors.
In addition, the definition of the abbreviation "NM" is incorrect; the correct definition is: "NM = diagonal bolted bridging not mandatory." The correct tables are printed below with the changes identified.
TABLE A — ERECTION BRIDGING FOR SHORT SPAN JOISTS
| Joist | Span |
|---|---|
| ~~8L1~~ 8K1 | NM |
| 10K1 | NM |
| 12K1 | 23-0 |
| 12K3 | NM |
| 12K5 | NM |
| 14K1 | 27-0 |
| 14K3 | NM |
| 14K4 | NM |
| 14K6 | NM |
| 16K2 | 29-0 |
| 16K3 | 30-0 |
| 16K4 | 32-0 |
| 16K5 | 32-0 |
| 16K6 | NM |
| 16K7 | NM |
| 16K9 | NM |
| 18K3 | 31-0 |
| 18K4 | 32-0 |
| 18K5 | 33-0 |
| 18K6 | 35-0 |
| 18K7 | NM |
| 18K9 | NM |
| 18K10 | NM |
| 20K3 | 32-0 |
| 20K4 | 34-0 |
| 20K5 | 34-0 |
| 20K6 | 36-0 |
| 20K7 | 39-0 |
| 20K9 | 39-0 |
| 20K10 | NM |
| 22K4 | 34-0 |
| 22K5 | 35-0 |
| 22K6 | 36-0 |
| 22K7 | 40-0 |
| 22K9 | 40-0 |
| 22K10 | ~~40-0~~ NM |
| 22K11 | ~~40-0~~ NM |
| 24K4 | 36-0 |
| 24K5 | 38-0 |
| 24K6 | 39-0 |
| 24K7 | 43-0 |
| 24K8 | 43-0 |
| 24K9 | 44-0 |
| 24K10 | NM |
| 24K12 | NM |
| 26K5 | 38-0 |
| 26K6 | 39-0 |
| 26K7 | 43-0 |
| 26K8 | 44-0 |
| 26K9 | ~~45-0~~ 44-0 |
| 26K10 | 49-0 |
| 26K12 | NM |
| 28K6 | 40-0 |
| 28K7 | 43-0 |
| 28K8 | 44-0 |
| 28K9 | 45-0 |
| 28K10 | 49-0 |
| 28K12 | 53-0 |
| 30K7 | 44-0 |
| 30K8 | 45-0 |
| 30K9 | 45-0 |
| 30K10 | 50-0 |
| 30K11 | 52-0 |
| 30K12 | 54-0 |
| 10KCS1 | NM |
| 10KCS2 | NM |
| 10KCS3 | NM |
| 12KCS1 | NM |
| 12KCS2 | NM |
| 12KCS3 | NM |
| 14KCS1 | NM |
| 14KCS2 | NM |
| 14KCS3 | NM |
| 16KCS2 | NM |
| 16KCS3 | NM |
| 16KCS4 | NM |
| 16KCS5 | NM |
| 18KCS2 | 35-0 |
| 18KCS3 | NM |
| 18KCS4 | NM |
| 18KCS5 | NM |
| 20KCS2 | 36-0 |
| 20KCS3 | 39-0 |
| 20KCS4 | NM |
| 20KCS5 | NM |
| 22KCS2 | 36-0 |
| 22KCS3 | 40-0 |
| 22KCS4 | NM |
| 22KCS5 | NM |
| 24KCS2 | 39-0 |
| 24KCS3 | 44-0 |
| 24KCS4 | NM |
| 24KCS5 | NM |
| 26KCS2 | 39-0 |
| 26KCS3 | 44-0 |
| 26KCS4 | NM |
| 26KCS5 | NM |
| 28KCS2 | 40-0 |
| 28KCS3 | 45-0 |
| 28KCS4 | 53-0 |
| 28KCS5 | 53-0 |
| ~~30KC53~~ 30KCS3 | 45-0 |
| 30KCS4 | 54-0 |
| 30KCS5 | 54-0 |
NM = diagonal bolted bridging not mandatory ~~for joists under 40 feet~~.
TABLE B — ERECTION BRIDGING FOR LONG SPAN JOISTS
| Joist | Span |
|---|---|
| 18LH02 | 33-0 |
| 18LH03 | NM. |
| 18LH04 | NM. |
| 18LH05 | NM. |
| 18LH06 | NM. |
| 18LH07 | NM. |
| 18LH08 | NM. |
| 18LH09 | NM. |
| 20LH02 | 33-B0 |
| 20LH03 | 38-0 |
| 20LH04 | NM. |
| 20LH05 | NM. |
| 20LH06 | NM. |
| 20LH07 | NM. |
| 20LH08 | NM. |
| 20LH09 | NM. |
| 20LH10 | NM. |
| 24LH03 | 35-0 |
| 24LH04 | 39-0 |
| 24LH05 | 40-0 |
| 24LH06 | 45-0 |
| 24LH07 | NM. |
| 24LH08 | NM. |
| 24LH09 | NM. |
| 24LH10 | NM. |
| 24LH11 | NM. |
| 28LH05 | 42-0 |
| 28LH06 | ~~42-0~~ 46-0 |
| 28LH07 | ~~NM.~~ 54-0 |
| 28LH08 | ~~NM.~~ 54-0 |
| 28LH09 | NM. |
| 28LH10 | NM. |
| 28LH11 | NM. |
| 28LH12 | NM. |
| 28LH13 | NM. |
| 32LH06 | 47-0 through 60-0 |
| 32LH07 | 47-0 through 60-0 |
| 32LH08 | 55-0 through 60-0 |
| 32LH09 | NM through 60-0 |
| 32LH10 | NM through 60-0 |
| 32LH11 | NM through 60-0 |
| 32LH12 | NM through 60-0 |
| 32LH13 | NM through 60-0 |
| 32LH14 | NM through 60-0 |
| 32LH15 | NM through 60-0 |
| 36LH07 | 47-0 through 60-0 |
| 36LH08 | 47-0 through 60-0 |
| 36LH09 | 57-0 through 60-0 |
| 36LH10 | NM through 60-0 |
| 36LH11 | NM through 60-0 |
| 36LH12 | NM through 60-0 |
| 36LH13 | NM through 60-0 |
| 36LH14 | NM through 60-0 |
| 36LH15 | NM through 60-0 |
~~NM = diagonal bolted bridging not mandatory for joists under 40 feet.~~
We anticipate making these changes through a technical correction to the standard, and also noting the changes in our upcoming revision to the steel erection directive [CPL 02-01-034 (formerly CPL 2-1.34)].
We appreciate your bringing these problems to our attention. We value our cooperative relationship with SJI and appreciate the extraordinary amount of time and effort your organization has provided throughout the steel erection rulemaking process.
If you need additional information, please contact us by fax at: U.S. Department of Labor, OSHA, Directorate of Construction, [Office of Construction Standards and Guidance], fax # 202-693-1689. You can also contact us by mail at the above office, Room N3468, 200 Constitution Avenue, N.W., Washington, D.C. 20210, although there will be a delay in our receiving correspondence by mail.
Sincerely,
Russell B. Swanson, Director
Directorate of Construction
[Corrected 6/2/2005]