Ventilation rate for aircraft spray painting areas

Summary The Navy asked what ventilation rate applies to aircraft corrosion-control hangars used for spray painting. OSHA said the cited standards set no single flow rate for spray areas; ventilation must control vapors and residues and keep exhaust vapor concentrations below 25 percent of the lower flammable limit. OSHA treated the described hangars as spray areas because painting was incidental to other work, and identified related training and protective-equipment duties.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1997-04-08-0
Date issued
April 8, 1997
Status
Active
Status last verified October 9, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

April 8, 1997
Ms. Elsie L. Munsell
Deputy Assistant Secretary of the Navy
(Environment and Safety)
Department of the Navy
[Recipient address omitted]
Dear Ms. Munsell:
This is in response to your letter of March 14 requesting an interpretation of the Occupational Safety and Health Administration (OSHA) standard for the airflow rate required for a spray painting area.
29 CFR 1910.94(c) and 29 CFR 1910.107 both apply to spray areas. These sections are currently under revision and will be combined into one area of 29 CFR 1910.107. There is no specific flow rate mentioned in either standard for spray areas, OSHA uses National Fire Protection Association Publication, NFPA 33, 1995 edition, (copy enclosed) Spray Application Using Flammable or Combustible Materials, paragraph 5-2, which requires that "each spray area be provided with mechanical ventilation that is capable of confining and removing vapors and mists to a safe location and is capable of confining and controlling combustible residues, dusts, and deposits. The concentration of vapors and mists in the exhaust stream of the ventilation system shall not exceed 25% of the lower flammable limit." This means that the airflow may be variable depending on the job being performed. This also means that under the circumstances that you have described, OSHA considers these corrosion-control hangars to be spray areas as opposed to spray booths. The determining factor in this decision is that other work is also performed in the area and painting is incidental to the specific area that is being treated (wing, rudder, etc.), and not the entire aircraft on a repetitive basis.
The employees must also be fully trained in the hazards to which they are exposed and in the emergency action and fire protection plans required by 29 CFR 1910.38 [and 1910.39], in personal protective equipment as required in 29 CFR 1910 Subpart I and also in the health requirements listed in 29 CFR 1910 Subpart Z.
Should you have further questions, please contact [the Office of General Industry Enforcement at (202) 693-1850].
Thank you for your continued interest in occupational safety and health.
Sincerely,
John E. Plummer, Director
Office of Federal Agency Programs
Enclosure

[Requester letter reproduced on OSHA page; omitted here.]

What does federal law require in your situation?

Ezel checks current federal labor law against your facts and answers with citations.

Opens in Ezel Pro.

  • Checks the law as it stands today, not only this page
  • Cites every source it relies on, so you can verify it
  • Chat, drafting and research in one workspace