Time-delay relays on gas-fired bakery ovens

Summary A bakery equipment operator asked if an oven's interlocked fuel-safety system could use a time-delay relay. OSHA said the standard did not permit a delay in the power control line: failure of ignition current must shut off both the high-tension circuit and fuel supply simultaneously.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1994-12-13-1
Date issued
December 13, 1994
Status
Active
Status last verified October 9, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

December 13, 1994

Dick Kozyra, President
American Bakers Cooperative, Inc.
[Recipient address omitted]
Dear Mr. Kozyra:

This is in further response to your May 31, letter requesting interpretation of the Bakery Equipment Standard, 29 CFR 1910.263(l)(9)(iv)(a). Please accept our apology for the delay in re-sponding.

You requested clarification for ovens with time delay relay systems built into the power supply line, which is interlocked with the fuel safety valves. Specifically, you asked if all gas safeties, when tripped, must cause the gas safety valves to close immediately, or is a time delay legal?

The standard does not allow employers to install time delay relay systems in the power control line of ovens, when the power line is interlocked with the fuel supply.

The high-tension current for any electric spark-type ignition device must originate in a power supply line which is interlocked with the fuel line supply for the oven in such a way that in case of current failure both the source of electricity to the high tension circuits and the fuel supply shall be turned off simultaneously.

We appreciate your interest in employee safety and health. If we can be of further assistance please contact Mr. Russelle R. McCollough in the Office of General Industry Compliance Assistance, telephone number (202) 219-8031, extension 105.

Sincerely,

John B. Miles, Jr., Director
Directorate for Compliance Programs