Back to Federal guidance

Atmospheric tanks and batch-process PSM coverage

Summary A chemical company asked whether an atmospheric storage tank and a batch blending unit with temporary hose connections counted as one exempt process. OSHA said the facts were insufficient for a determination and explained that covered processing may include more than storage and associated transfer. OSHA labels the letter an archive document.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1994-08-08-2
Date issued
August 8, 1994
Status
Archived by the agency
OSHA labels this an archive document and warns that it may no longer represent current policy.
Status last verified October 9, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

The current status of this document is unclear
OSHA labels this an archive document and warns that it may no longer represent current policy. It may no longer reflect the agency's current position. Treat this page as historical context, not current guidance, and verify current law before relying on anything here.
About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

August 8, 1994

Mr. David W. Spencer
Baker Performance Chemicals, Inc.
[Recipient address omitted]
Dear Mr. Spencer:

This is in response to your June 16 letter requesting clarification of the Process Safety Management (PSM) of Highly Hazardous Chemicals (HHCs) standard, 29 CFR 1910.119 as it may apply to the batch chemical processes as described in the scenario below. Your question and our reply follow. Please accept our apology for the delay in responding.

Scenario: More than 10,000 pounds (4535.9kg) of flammable liquid, kept below its normal boiling point without benefit of chilling or refrigeration, is stored in an atmospheric tank. This flammable liquid is transferred by interconnected piping including temporary hosed to a blending unit. Before transfer, temporary hosed from the blending unit to other process units are disconnected. Also before transfer, the blending unit is rendered inoperative. After transfer of the flammable liquid to the blending unit is completed, the temporary hoses between the storage tank and the blending unit are disconnected. Subsequently, the temporary hoses between the blending unit and the other process units are connected and the blending unit is placed into operation. [The preceding scenario was amended for clarification during a August 3 telecon between you and Mr. Ron Davies of my staff.]

Question : Would the flammable liquid stored in the

atmospheric tank and transferred as described in the preceding scenario be considered a single process which would be excepted from PSM coverage by 29 CFR 1910.119(a)(1)(ii)(B)?

Reply: There is insufficient scenario information to answer your question. The following clarification is intended to assist you in determining whether your work site processes are covered by the PSM standard. The blending unit would have to meet the definition of atmospheric tank. The 1910.106 standard includes requirements for atmospheric tanks in which flammable liquids are stored. As such, the process which includes only the activities of flammable liquid storage and associated transfer between atmospheric tanks, that is, the storage tank and the blending unit, would be excepted from PSM coverage with the following exception. The flammable liquid atmospheric tanks and any separate vessels located nearby such that a highly hazardous chemical could be involved in a potential release are considered a single process (see the 1910.119(b) definition of "process"). When a separate vessel located nearby is part of another process which includes activities, that is handling, use, on-site movement or manufacturing in addition to storage and associated transfer activities, the 1910.119(a)(1)(ii)(B) exception would not apply.

If the work site employer intends to operate a process to avoid being subject to compliance with the PSM standard, it must have an effective program (and be prepared to demonstrate to the Occupational Safety and Health Administration (OSHA), that is, the Compliance Safety and Health Officer (CSHO) during an inspection of the work site, that such a program precludes a process, as described above, from being part of another process involving activities other than storage and associated transfer.

We appreciate your interest in occupational safety & health. If we may be of further assistance please contact us.

Sincerely,

John B. Miles, Jr., Director Directorate of Compliance Programs