Testing ground-fault circuit interrupters at construction sites

Summary OSHA instructed regional offices on testing construction-site ground-fault circuit interrupters. It said external testers could give inaccurate results and directed inspectors to use the built-in test circuit; an attached technical note explained the reasoning. OSHA archives the memo and warns it may no longer represent current policy.
Document
Federal guidance
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1994-02-16
Date issued
February 16, 1994
Status
Archived by the agency
OSHA labels this an archive document and warns that it may no longer represent current policy.
Status last verified October 9, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

The current status of this document is unclear
OSHA labels this an archive document and warns that it may no longer represent current policy. It may no longer reflect the agency's current position. Treat this page as historical context, not current guidance, and verify current law before relying on anything here.
About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

February 16, 1994

MEMORANDUM FOR: ALL REGIONAL ADMINISTRATORS

THROUGH: H. BERRIEN ZETTLER, DEPUTY DIRECTOR, DIRECTORATE OF COMPLIANCE PROGRAMS

FROM: ROY F. GURNHAM, DIRECTOR, OFFICE OF CONSTRUCTION AND MARITIME COMPLIANCE ASSISTANCE

SUBJECT: Testing Ground Fault Circuit Interrupters

The purpose of this memorandum is to reiterate the policy for testing ground fault circuit interrupters (GFCIs) used at construction sites.
GFCI testers which are not an integral part of the GFCI shall not be used as a means of determining compliance with 1926.404(b)(1)(ii) because such testers often do not produce accurate results. Only the testing circuit which is manufactured as part of the GFCI shall be used to determine whether or not the device will function as intended.
A copy of the Electrical/Electronic Technical Note 91-1, authored by the Office of Electrical, Electronic, and Mechanical Engineering Safety Standards, is attached for additional information and guidance.
If you have any questions, please contact me or Dale Cavanaugh of my staff at (202) 219-8136.
Attachment.

Electrical/Electronic Technical Note 91-1
December 18, 1991
How to Test the Operation of a GFCI

The Office of Electrical, Electronic, and Mechanical Engineering Safety Standards does not recommend the use of GFCI testers as a means of determining compliance with 1926.404(b)(1)(ii), as such testers may not produce accurate results. Ground-fault circuit interrupters incorporate a testing circuit that can be used to determine whether or not the device itself will function as intended. No further tests are necessary.
Any GFCI tester that puts a resistive load between the ungrounded circuit conductor and the equipment grounding conductor⁽¹⁾ to measure the current at which the device trips is subject to errors due to voltage fluctuations. If the circuit voltage is 100 volts, the tester could indicate that a GFCI tripped at 7.2 mA when it would actually have tripped at 6.0 mA. (See attachment.)
Testers like the Greenlee model 5708,⁽²⁾ described in Mr. Loebach's memorandum, cannot produce a reliable indication of the trip level of a GFCI. This device sends a 200-millisecond pulse through the grounding conductor at various current levels. A GFCI may not trip at minimum current levels (that is, 6-20mA) in such a short period of time. (For example, UL Standard 943 allows trip times of up to 1.5 seconds at 15mA.) This tester provides a 4-second interval between pulses and cannot be adjusted to provide a longer pulse or a shorter interval.
Additionally, an employer cannot reasonably be expected to know at what level his or her GFCIs trip. A reasonable person would only expect the employer to check them periodically using their built-in test mechanisms. Assuming that test equipment could accurately detect a GFCI that trips at too high a current, the employer should not be penalized for conditions beyond his or her normal control. A citation in such cases may be warranted--penalties are not.
The supervisory circuit built into a ground-fault circuit interrupter is designed to cause tripping even when the circuit voltage is 85 percent of rated voltage (102V for a 120-volt device). At rated voltage, the current employed by the supervisory circuit may not exceed 9mA. Thus, it gives an indication of the operability of the GFCI at currents approaching the trip level. It may not give an indication of whether the GFCI actually opens the circuit; however, this can easily be determined by plugging utilization equipment into the circuit in question.
For these reasons, the Office of Electrical, Electronic, and Mechanical Engineering Safety Standards recommends that the compliance staff use the test button on a GFCI in combination with an attached load plugged into the circuits to be tested rather than a GFCI tester. A plug-in ground continuity tester would suffice as an attached load. If the lights on the continuity tester go out when the test button is pressed, the GFCI can be assumed to be operating correctly. If the lights stay on or if the test mechanism fails to operate, the GFCI is faulty, and a citation would be warranted.

Footnote (1) Deliberately putting current through the equipment grounding conductor is undesirable and, under certain conditions (for example, in a hazardous location), is unsafe.

Footnote (2) This device is not currently approved by a nationally recognized testing laboratory and does not meet OSHA's electrical safety standards. Therefore, it should not be used by OSHA compliance staff.

[A December 21, 1993, company letter reproduced on OSHA's page follows the technical note; omitted here.]

What does federal law require in your situation?

Ezel checks current federal labor law against your facts and answers with citations.

Opens in Ezel Pro.

  • Checks the law as it stands today, not only this page
  • Cites every source it relies on, so you can verify it
  • Chat, drafting and research in one workspace