Power strips used for surge protection or extra outlets

Summary An OSHA safety committee asked when workplace power strips violated electrical rules. OSHA distinguished devices used for surge suppression from strips used solely to add convenient outlets, which OSHA said violated the rule against substituting flexible cords for fixed wiring, and urged an overload assessment.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1993-06-11-0
Date issued
June 11, 1993
Status
Archived by the agency
OSHA labels this an archive document and warns that it may no longer represent current policy.
Status last verified October 9, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

The current status of this document is unclear
OSHA labels this an archive document and warns that it may no longer represent current policy. It may no longer reflect the agency's current position. Treat this page as historical context, not current guidance, and verify current law before relying on anything here.
About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

June 11, 1993

Mr. Rick Cee
Chairperson, OSHA-SLTC
Safety Committee
U.S. Department of Labor
Occupational Safety and Health
Administration
Salt Lake City Technical Center
[Recipient address omitted]
Dear Mr. Cee:

This is in response to your letter of February 26, regarding the use of "power strips". You apparently want our opinion on whether certain working conditions relative to the described "power strips" might constitute a violation of OSHA standards. You were also concerned about the cost of abatement should a violation exist. Please accept our apologies for the delay in the response.

"Power strips" as mentioned in your letter or "surge/noise protective strips" as termed in the literature you sent as enclosures are generally referred to as temporary power taps. Temporary power taps that incorporate switches, indicator lights, filters for electromagnetic interference, fuses, varistors, or other overcurrent mechanisms in their design could be devices for transient voltage surge suppression of equipment. Transient voltage surge suppressors when used to preserve the components of the equipment listed in your letter (computer, printer, fax, miscellaneous appliances and analytical instruments) could be considered a device as defined in 29 CFR 1910.399:

Device. A unit of an electrical system which is intended to carry but not utilize electric energy.

If the temporary power taps are being used to provide transient voltage surge suppression, then these devices would meet the OSHA standards. If the temporary power taps are being used solely as wiring to provide extra or more convenient outlets, then this is a violation of 29 CFR 1910.305(g)(1)(iii)(A):

... flexible cords and cables may not be used:

(A) As a substitute for the fixed wiring of a structure;....

The selection of the surge/noise protective devices should be made following the manufacturer's recommendations for each piece of equipment that is to have this safeguard. An assessment of the electric branch circuits in the facility should be made to assure there is no potential for an electric overload situation where the equipment is used.

If you should need further assistance please do not hesitate to contact us.

Sincerely,
Raymond Donnelly, Director
Office of General Industry Compliance