Summary A contractor asked whether ground fault circuit interrupters on cords and portable tools eliminate the need for an assured equipment grounding conductor program. OSHA said fully approved GFCI assemblies that protect the entire length of every cord can satisfy the construction rule without that program. If some cord sets lack GFCI protection, the employer needs the grounding program and must test all cord sets and plug-connected equipment, including GFCI-equipped items.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1992-11-04-1
Date issued
November 4, 1992
Status
Active
Status last verified October 10, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

November 4, 1992

Ernest Breaux, Jr.
Bechtel Environmental
[Recipient address omitted]
Dear Mr. Breaux:

This is in response to your August 31 letter requesting an interpretation of an Occupational Safety and Health Administration (OSHA) standard addressing ground fault circuit interrupters on extension cords as well as on portable tools. I apologize for the delay in our response.

Paragraph 1926.404(b)(1) requires an employer to use either ground fault circuit interrupters (GFCI) or an assured equipment grounding conductor program to protect employees on construction sites. The GFCI equipped cord set assembly or the GFCI equipped portable tool assembly must, as a complete unit, be approved as required by 1926.403(a) in accordance with the definition given in 1926.449. If all incorporated GFCI cord sets and/or portable tool assemblies at a construction site are approved and used in a manner such that the entire length of all cords are provided with protection, then the employer would be in compliance with this standard without an assured equipment grounding conductor program. A problem may arise, however, if some but not all cord sets are equipped with GFCI's. In this case, an assured equipment grounding conductor program would be required for all cord sets and equipment connected by cord and plug, as established in paragraph 1926.404(b)(1)(iii). In other words, this would require the testing of all cord sets including those cord sets and portable tools which incorporate their own individual approved GFCI's.

If we can be of any further assistance please contact either myself or Dale R. Cavanaugh of my staff at (202) 219-8136.

Sincerely,
Roy F. Gurnham, Esq., P.E.
Director
Office of Construction and Maritime
Compliance Assistance

[Requester letter reproduced on OSHA page; omitted here.]

What does federal law require in your situation?

Ezel checks current federal labor law against your facts and answers with citations.

Opens in Ezel Pro.

  • Checks the law as it stands today, not only this page
  • Cites every source it relies on, so you can verify it
  • Chat, drafting and research in one workspace