Back to Federal guidance

Halon 1301 fire and explosion suppression systems

Summary An OSHA regional office sought guidance on workplace Halon 1301 systems used for both fire and explosion suppression. OSHA said section 1910.162 applies to fire suppression, while OSHA standards do not specifically address Halon as an explosion suppression agent. It identified the grain-handling provision and said hazards from a system used only for explosion suppression may be addressed under the Act's general duty clause.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1991-07-11-0
Date issued
July 11, 1991
Status
Active
Status last verified October 9, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

July 11, 1991

MEMORANDUM FOR: LINDA ANKU
REGIONAL ADMINISTRATOR, III

FROM: PATRICIA K. CLARK, DIRECTOR
DIRECTORATE OF COMPLIANCE PROGRAMS

SUBJECT: Manufacturer Supplying Halon 1301 Systems for Fire and
Explosion Suppression

This memorandum is in response to your May 23 memorandum with enclosures on employer use of Halon 1301 for explosion and fire suppression in the workplace. Specifically, the following guidance is provided with respect to questions posed in the May 8 memorandum to you from the Pittsburgh Area Office.

The only OSHA standard which addresses explosion suppression systems is 29 CFR 1910.272(p)(8)(i) on grain handling facilities. However, use of Halon as an explosion suppression agent is not addressed by any OSHA standards. Fire suppression systems are covered by 29 CFR 1910.162. Apparently, the 1301 Halon system described in the internal Penn Champ Inc. memorandum of October 22, 1987, is installed to suppress explosions in conjunction with the use of pressure and radiant energy detectors, and to suppress fires in conjunction with the use of thermal detectors. Therefore, 29 CFR 1910.162, which covers fire suppression systems, is applicable to the latter combination. Workplace safety and health hazards associated with Halon 1301 systems used exclusively for explosion suppression are citable under section 5(a)(1) the OSH Act. For your information, the 1986 edition of NFPA 69 standard addresses "Explosive Prevention Systems".

Halon 1301 itself and associated products of combustion provide a potential hazard to employees. These hazards are addressed in A-1-6.1 of Appendix A of the NFPA 12A standard on Halon 1301 Fire Extinguishing Systems. The employer can meet OSHA standards for storage and handling of flammable and combustible liquids by means exclusive of explosion prevention systems, including the explosion suppression method employing Halon 1301.