Grounding a construction transformer secondary circuit
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.
February 24, 1988
MEMORANDUM FOR: LINDA R. ANKU
Regional Administrator
THRU: LEO CAREY, Director
Office of Field Programs
FROM: THOMAS J. SHEPICH, Director
Directorate of Compliance Programs
SUBJECT: Review of Electrical Utilities Procedures for Compliance with Subpart K of Part 1926
29 CFR 1926.404(f)(1)(iv) requires AC systems of 50 to 1000 volts to be grounded if the system can be so grounded that the maximum voltage to ground will not exceed 150 volts. (29 CFR 1910.304(f)(1)(iv) contains a similar requirement for general industry.) A system supplied by a transformer whose secondary voltage is 120 volts between conductors (or is 120 volts between each line conductor and a common neutral and 240 volts between the line conductors) must be grounded. Therefore the installation described in the attachment to Mr. Forbes' letter is in violation of this requirement. Grounding the system described by Mr. Forbes will protect the secondary circuit conductors from having the primary voltage impressed on them (in this case 600 volts) and will limit the voltage above ground on the secondary conductors.
What does federal law require in your situation?
Ezel checks current federal labor law against your facts and answers with citations.
Opens in Ezel Pro.
- Checks the law as it stands today, not only this page
- Cites every source it relies on, so you can verify it
- Chat, drafting and research in one workspace