Steel cable guardrails around floor edges

Summary A developer asked whether steel cable could serve as top and intermediate rails around a floor edge. OSHA said the proposed system might comply if the cables were taut, secured and met the stated load and deflection criteria, and if toeboards or equivalent protection were provided for workers below. OSHA now archives the letter as potentially outdated.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1985-11-14
Date issued
November 14, 1985
Status
Archived by the agency
OSHA archives this document and says it may no longer represent OSHA policy.
Status last verified October 10, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

The current status of this document is unclear
OSHA archives this document and says it may no longer represent OSHA policy. It may no longer reflect the agency's current position. Treat this page as historical context, not current guidance, and verify current law before relying on anything here.
About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

November 14, 1985

Mr. Frank Wood
Franklin Plaza Development Company
[Recipient address omitted]
Dear Mr. Wood:

This is in response to your letter of August 23, concerning your request for a variance from 29 CFR 1926.500(d)(1). Your letter was forwarded to this office for a clarification of our standard railing requirements.

29 CFR 1926.500(f)(1)(vi) provides the specification criteria for a standard railing exception as follows:

(vi) Other types, sizes, and arrangements of railing construction are acceptable, provided they meet the following conditions:

(a) A smooth-surfaced top rail at a height above floor, platform, runway, or ramp level of approximately 42 inches;

(b) A strength to withstand at least the minimum requirements of 200 pounds top rail pressure with a minimum of deflection;

(c) Protection between top rail and floor, platform, runway, ramp, or stair treads, equivalent at least to that afforded by a standard intermediate rail;

(d) Eliminations of overhang of rail ends unless such overhang does not constitute a hazard.

Your proposal to install a 9/16 inch standed steel cable attached to columns approximately 42 inches for the top rail and 21 inches for the intermediate rail, appears to meet the intent of our railing requirements. However, the wire ropes shall be secured to each support and taut at all times. In addition the maximum deflection of the top rail when a load of 200 pounds is applied in any direction at any point on the top rail shall not exceed 3 inches in one direction. The intermediate post may be omitted provided the above mentioned criteria for the steel cables is satisfied.

The vertical barrier (toeboard) at floor level erected along exposed edges of a floor opening must be installed to prevent falls of materials on employees working below the floor. Toeboards could be deleted only in situations where other type equivalent protection is provided. The ledge of 2 feet inside the perimeter does not provide equivalent protection.

Your enforcement of the requirement that employees must wear an approved safety belt and be attached to the cable or columns by means of an approved short safety lanyard (2 feet or less) when working between the cable an the perimeter of the building would be acceptable.

It appears based on the information you have provided, that your guardrail system with the inclusion of toeboards could comply with 29 CFR 1926.500(f)(1)(vi), if properly installed and maintained.

If we can be of further assistance, please let us know.

Sincerely,
John B. Miles, Jr., Director
Directorate of Field Operations