Summary A company asked which flammable-liquid storage provisions applied to indoor tanks associated with acid tank vehicle loading. OSHA said the described facility appeared to be a unit physical operation, so relevant indoor tank and handling provisions could apply. It said the bulk plant provision did not appear to apply.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1982-08-27
Date issued
August 27, 1982
Status
Active
Status last verified October 10, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

August 27, 1982

Mr. William Jones
Environmental Engineer
Halliburton Services
Department of Government Regulations
[Recipient address omitted]
Dear Mr. Jones:

Thank you for your letter of July 26, 1982, requesting an interpretation of certain 29 CFR 1910.106 standards for your operation of indoor tank storage and handling of flammable and combustible liquids. This also confirms a telephone discussion of the subject matter with a member of my staff, Mr. Peter Wasko, in which you pointed out that liquid is added in very small amounts to mix with the acid in your 500-4,000 gallons-capacity acid tanks vehicles at the loading dock located up to 25 feet from the building.

Your operation, as indicated above, appears to be a unit physical operation covered by 29 CFR 1910.106(e)(1)(i)(b) and (3) (copies enclosed). Note that 1910.106(e)(3)(vi) requires that storage, transfer, and handling of liquid be according to 1910.106(h)(4) and that 1910.106(h)(4)(i)(b) and (i)(c) (copy enclosed) permit storage tanks inside buildings according to 1910.106(b), where 1910.106(b)(4) would apply (copy enclosed). Hence, the relevant requirements of 29 CFR 1910.106(e), as indicated in this paragraph, could apply to your indoors storage tanks.

In regards to the applicability of 29 CFR 1910.106(f), it appears that the facility concerning you is a unit physical operation facility and not a bulk plant. Hence, 29 CFR 1910.106(f) would not apply.

In regards to the applicability of 29 CFR 1910.106(b)(4)(i), the more specific standards where they exist, as in 29 CFR 1910.106(h)(4)(i)(b) and (i)(c), would take precedence over any more general relevant standard.

Should you have any further questions, please do not hesitate to contact Mr. Peter Wasko, of this office at 202/523-8124.

Sincerely,

Patrick R. Tyson
Director, Federal Compliance
and State Programs