Manual fire alarms and employee emergency plans
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
June 26, 1981
Mr. Thomas A. Duym
Safety Administrator
Special Products Division
Nabisco, Inc.
[Recipient address omitted]
Dear Mr. Duym:
This is in response to your recent inquiry regarding supervised manual fire alarm systems and 29 CFR 1910.165. The requirement of 1910.165(a)(1), that employers have an alarm system, applies only to those employers who choose to have employee emergency plans as indicated in 1910.38.
There is presently no requirement to install manual fire alarm systems; however, if they are installed and are capable of being supervised, the requirements of 1910.165(d) would apply.
The public address, bell paging, fire gong, bull horn and/or personal communicators must comply with 1910.165(b)(1)-(b)(5) if the employer has an employee emergency plan.
Fire alarm systems for grain elevators must also comply with the appropriate requirements of 29 CFR 1910 Occupational Safety and Health Standards - Fire Protection, [Exit Routes], and Hazardous Materials only if the employer has an emergency action plan.
We hope this information will be of assistance to you.
Sincerely,
John K. Barto Chief,
Division of Occupational Safety Programming
[Corrected 2/4/2004]