Back to Federal guidance

Electronic release buttons on exit doors

Summary A company asked about a security door with an electronic release button. OSHA said employees must be able to open an exit route door immediately from inside without a preliminary action; an added button before the panic bar violated the rule’s intent. A security signal that did not inhibit exit was permissible.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1981-03-12
Date issued
March 12, 1981
Status
Active
Status last verified October 10, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

March 12, 1981
Mr. William B. Reitze
Vice President
Chief Environmental Scientist Health,
Safety and Environment Department
Johns-Manville Sales Corporation
[Recipient address omitted]
Dear Mr. Reitze:
This is in response to your correspondence regarding your security door lock system presently installed in the Research and Development building.
29 CFR [1910.36(d)(1)] requires that ["Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar that locks only from the outside is permitted on exit discharge doors"].
The use of an electronic device that must be pressed before the panic bar can be activated violates the intent of 29 CFR [1910.36(d)(1)]. Employers utilizing such a system are cited. Employees trying to evacuate a smoke filled room may not be able to locate the electronic device and would be trapped at the exit door. Depression of the panic bar must open the exit without any prior action. Relays which signal a security monitor of the occurrence and which do not inhibit exiting are permitted.
It is suggested that Mr. Steve Crown, Branch Manager, Protection Services at Honeywell in Denver, be contacted for assistance in correcting the installation deficiency. Mr. Crown may be reached at telephone number 303-741-3002.
If we may be of further assistance, please call or write.
Sincerely,
Bruce Hillenbrand
Deputy Director, Federal
Compliance and State Programs
[Correction 2/6/2004]