Reversed polarity in electrical receptacles
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
February 18, 1980
MEMORANDUM FOR: GILBERT J. SAULTER
Regional Administrator
ATTENTION: HERBERT M. KURTZ
THRU: ROGER CLARK
Field Coordinator
FROM: GROVER C. WRENN
Director Federal Compliance and State Programs
SUBJECT: Citing of Reversed Polarity
In response to your inquiry on reversed polarity in requirement for correct polarity in receptacles is indicated by the 1971 National Electrical Code sections 200-2, 200-9, and 200-10(b). These sections require the grounded conductor to be properly identified. If the grounded conductor is connected to the wrong terminal in a receptacle, it is no longer correctly identified. Also, Sections 200-7 generally prohibits ungrounded conductors from being identified with a white or natural gray color. This requirement would be violated if the ungrounded conductor were connected to the identified terminal. In the 1978 NEC and in the Office of Standards Development proposed revision of Subpart S, there is a new requirement covering reversed polarity specifically.
The hazards of reversed polarity are discussed in the two enclosures.