Summary A utility asked how OSHA’s transmission-line grounding provisions fit together. OSHA said clipping and tying crews on bare conductors had to work between grounds. Other overhead-line work could proceed without grounding only under the stated conditions concerning induced voltage, clearances, and protection from energized equipment.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1978-09-21
Date issued
September 21, 1978
Status
Active
Status last verified October 10, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

September 21, 1978

Mr. G. A. Mudrick
Assistant Safety Director
Pennsylvania Powe
and Light Company
[Recipient address omitted]
Dear Mr. Mudrick:

This is in response to your letter requesting an interpretation of 29 CFR 1926.955(c)(10) in its entirety and as it relates to 29 CFR 1926.954(b)(2) and 29 CFR 1926.955(c)(3). The OSHA Philadelphia Regional Office forwarded your letter to this office for reply. Please accept my apology for the delay in response.

29 CFR 1926.955(c)(10) does require transmission clipping and tying crews to work between grounds at all times when working on bare conductors. However, other overhead line work may be performed on ungrounded conductors provided the hazard of induced voltages is not present, and adequate clearances or other means are implemented to prevent contact with energized lines or equipment and the new lines or equipment as indicated in 29 CFR 1926.954(b)(2).

In work situations where the hazard of induced voltages is present, and adequate clearances or other means are not implemented to prevent contact with energized lines or equipment and the new lines or equipment, the lines or equipment shall be grounded or provisions made to insulate or isolate the employee as indicated in 29 CFR 1926.955(c)(3). The 29 CFR 1926.955(c)(10) is a specific requirement and the other two standards are general requirements.

If I may be of any further assistance, please feel free to contact me.

Sincerely,
John K. Barto, Chief
Division of Occupational