Tunnel ventilation at atmospheric and compressed pressure
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
November 11, 1975
Mr. Charles A. Della
Assistant Commissioner
Department of Licensing and Regulation
[Recipient address omitted]
Dear Mr. Della:
In response to your letter of October 21, 1975 concerning 29 CFR 1926.800(c)(2)(v) and 29 CFR 1926.803(i)(1) we concur with the interpretations indicated in your letter.
- [29 CFR 1926.800(k)(2)]: Requires the supply of fresh air to be not less than 200 cubic feet per minute for each employee in a tunnel work area where operations are conducted at atmospheric pressure. This standard does not apply to compressed air work.
- 29 CFR 1926.803(i)(1): The sentence "Ventilating air shall be not less than 30 cubic feet minute." Means not less than 30 cubic feet minute man during compressed air work.
Sincerely yours,
DAVID H. RHONE
Assistant Regional Director
Occupational Safety and Health Administration
[Corrected 05/28/2004]