Lighting fixtures near spray booths
Apply this to your situation
This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.
NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.
April 14, 1975
Mr. George Cory
[Recipient address omitted]
Dear Mr. Cory:
This is in response to your letter requesting clarification of standards approving lighting fixtures in spray booths.
OSHA may not approve products by law. It merely sets standards which must be met by industries having exposures involving the safety and health of employees.
In the case of spray booth lighting the OSHA standard, 1910.107(b)(10) and (c)(7), states that illumination shall have fixed lighting units outside of the spray booth permitting light to enter through transparent panels. Such fixtures shall be totally enclosed if they are within 20 feet of the spray booth. In addition, compliance with the National Electrical Code NFPA 70-1971 is also mandatory.
We have mailed, under separate cover, several OSHA brochures including the Federal Register noted above. Please feel free to contact us if there are further questions about OSHA.
Very truly yours,
John J. Kearney
Associate Assistant Regional Director
for Technical Support/OSH