Back to Federal guidance

Cable and chain guards at construction openings

Summary An OSHA regional memo addressed cable and chain barriers at construction floor and wall openings. It set regional criteria for strength, anchoring, tension, visibility, and toeboards so those barriers would protect workers. OSHA archives the memo.
Document
Federal opinion letter
Agency
Occupational Safety and Health Administration (OSHA)
Document number
1973-12-23
Date issued
April 23, 1973
Status
Archived by the agency
OSHA labels this an archive document and warns that it may no longer represent OSHA policy.
Status last verified October 10, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

The current status of this document is unclear
OSHA labels this an archive document and warns that it may no longer represent OSHA policy. It may no longer reflect the agency's current position. Treat this page as historical context, not current guidance, and verify current law before relying on anything here.
About this page: The full text below is the official document from Occupational Safety and Health Administration (OSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

NOTICE: This is an OSHA Archive Document, and may no longer represent OSHA Policy. It is presented here as historical content, for research and review purposes only.

DATE:
April 23, 1973

REPLY TO
ATTN OF:
OSHA - ARA's Federal/State Operations - Technical Support

SUBJECT:
1926.500, Guardrails, handrails & guards

TO: ALL AREA DIRECTORS

Paragraph 1926.500(f)(l)(vi) provides for the utilization of types, sizes and arrangements of railing construction provided they meet the conditions established in sub-paragraph a thru d.

In construction the use of cables or chains to guard door and wall openings is common practice; however, unless these chains or cables are of sufficient size and strength to support the loads which might be imposed, they imply a security which is not present.

Since cables or chains are commonly used as barriers or guards on construction projects at floor and wall openings and to establish uniformity in this Region, the following criteria will govern the use of cable and chain as guards.

  1. Cable shall be not less than 3/8 inch mild plow steel.
  2. Chain shall be not less than 1/4 inch alloy steel.
  3. The chain or cable shall be anchored at intervals not to exceed 100 feet. These anchors shall be of sufficient strength to support the imposed loads without deflection.
  4. The chain or cable shall be provided with positive tensioning device (such as a turnbuckle) which will reduce the sag in the chain or cable to not more than 2 inches in a 20 foot span.
  5. Intermediate supports shall be installed in such a manner that they will provide the strength and spacing outlined for Posts in 1926.500(f)(l)(i), (ii) & (iii).
  6. The tensioning device shall have a breaking strength of not less than 10,000 pounds.
  7. The chain or cable shall be equipped with flagging or some other means of increasing their visibility.
    Chain or cable may be used as immediate rails when installed to the above criteria.
  8. Toeboards shall be 4 inches minimum in vertical height and of any material which will provide the strength equivalent to a Standard Southern Pine 1 inch by 4 inch board. These toeboards shall be secured in place as required by the Standards.

R. A. WENDELL
Assistant Regional Administrator
for Federal/State Programs.

What does federal law require in your situation?

Ezel checks current federal labor law against your facts and answers with citations.

Opens in Ezel Pro.

  • Checks the law as it stands today, not only this page
  • Cites every source it relies on, so you can verify it
  • Chat, drafting and research in one workspace