Identifying coal mine electrical circuits

Summary MSHA clarifies how coal mines should identify electrical circuits so workers can see that equipment power is disconnected. The breaker, receptacle, and trailing cable plug must carry similar labels under the cited rules. This reduces the chance of energizing a circuit while repairs are underway.
Document
Federal administrative policy
Agency
Mine Safety and Health Administration (MSHA)
Document number
P12-V-07
Date issued
May 22, 2012
Status
Active
MSHA lists this letter as last validated 2026-03-26, with an expiration date of 2028-03-31.
Status last verified October 24, 2026

Apply this to your situation

This page explains the general guidance. Ask about your specific situation and see what current federal labor law says, with citations.

About this page: The full text below is the official document from Mine Safety and Health Administration (MSHA). Ezel adds the plain-English summary and tracks the document's status. The official source linked on this page is authoritative for any reliance.

EFFECTIVE DATE: 5/22/2012
EXPIRATION DATE: 3/31/2028
LAST VALIDATED: 3/26/2026

PROGRAM POLICY LETTER NO. P12-V-07

FROM:
KEVIN G. STRICKLIN
Administrator for
Coal Mine Safety and Health

SUBJECT:
Circuit Identification under 30 C.F.R. § 75.903 and 75.904

Scope

This Program Policy Letter (PPL) applies to coal mine operators, Coal Mine Safety and Health Administration (MSHA) enforcement personnel and other interested parties.

Purpose

The purpose of this PPL is to clarify how electrical circuits should be identified under 30 C.F.R. § 75.903 to provide visual evidence that the power to equipment is disconnected to ensure safe operation and maintenance of the equipment.

Policy

Section 75.903, Disconnecting Devices, requires that a disconnecting device be installed in conjunction with the circuit breaker to provide visual evidence that the power is disconnected.

Section § 75.904 requires circuit breakers to be marked for identification. Additionally, § 75.601 requires disconnecting devices used to disconnect power from trailing cables to be plainly marked and identified and designed in a manner to be able to determine by visual observation that the power is disconnected.

A "disconnecting device" includes both a trailing cable plug (cathead) and the receptacle into which it is plugged. To provide visual evidence that the power is disconnected between the circuit breaker and disconnecting device, all three components -- the circuit breaker, the receptacle, and the trailing cable plug -- must be labeled in a similar manner. For example, the trailing cable plug, receptacle and circuit breaker serving loading machine #1 should each be labeled "Loader #1." Labeling disconnecting devices and circuit breakers in a similar manner, for example, with the name of the equipment being energized, will reduce the chance of energizing the circuit while repairs are being made to the equipment.

Background

MSHA has received questions on labeling requirements involving circuit breakers, trailing cable plugs, and receptacles. There have been several accidents involving repairs to electric equipment and inadequate labeling of circuits.

Authority

The Federal Mine Safety and Health Act of 1977, as amended, 30 U.S.C. § 801 et seq., and 30 C.F.R. §§ 75.601, 75.903, and 75.904.

Internet Availability

This PPL may be viewed on the Internet by accessing MSHA home page (www.msha.gov) and then choosing“Compliance Info” and “Program Policy Letters.”

Issuing Office and Contact Persons**

Coal Mine Safety and Health, Division of Safety
Rodney Adamson, (202) 693-9549
E-mail: adamson.rodney@dol.gov

Distribution

MSHA Program Policy Manual Holders
Special Interest Groups
Coal Mine Operators

*Per PIB P14-04 the expiration date was removed.
**Contact information was updated on 7/25/14.