Secretary of Labor (MSHA) v. Lava Products, Inc. (ALJ decision, November 19, 1985)
Secretary of Labor (MSHA) v. Lava Products, Inc. (FMSHRC WEST 84-72-M): Five electrical citations affirmed with reduced penalties
Apply this to your situation
This order from 1985 bound only the parties to this case; it isn't precedent. Ask about your situation and see what the current MSHA standards and Commission precedent say, with citations.
Plain-English summary
MSHA cited Lava Products, Inc., which operated the Veyo Mine, for five electrical safety violations. The company admitted the violations and contested only the proposed penalties. Judge John J. Morris found the electrical hazards serious and rejected an unsupported claim that the penalties might bankrupt the company. He credited the company's prompt correction of three conditions and reduced the penalties for those citations from $225 each to $125 each. The other two penalties remained $420 each, for a total assessment of $1,215.
Decision snapshot
- Cited standards: 30 C.F.R. §§ 55.12-25, 55.12-2, 55.12-40, 55.12-65, and 55.12-1, electrical safety requirements.
- Outcome: All five citations affirmed; three penalties reduced; $1,215 total assessed.
- Key point: Prompt abatement reduced penalties for three violations, while unsupported financial hardship did not justify a further reduction.
Full text (FMSHRC public release)
CCASE:
SOL (MSHA) v. LAVA PRODUCTS
DDATE:
19851119
TTEXT:
~1921
Federal Mine Safety and Health Review Commission Office of Administrative Law Judges
SECRETARY OF LABOR,
CIVIL PENALTY PROCEEDING
MINE SAFETY AND HEALTH
ADMINISTRATION (MSHA),
Docket No. WEST 84-72-M
PETITIONER
A.C. No. 42-01638-05501
v. Veyo Mine
LAVA PRODUCTS, INC.,
RESPONDENT
DECISION
Appearances: JayLynn Fortney, Esq., Office of the Solicitor, U.S. Department of Labor, Kansas City, Missouri, for Petitioner;
Mr. Samuel N. Rucker, President, Lava Products, Inc., Washington, Utah, pro se.
Before: Judge Morris
The Secretary of Labor, on behalf of the Mine Safety and Health Administration, charges respondent with violating five safety regulations promulgated under the Federal Mine Safety and Health Act, 30 U.S.C. 801 et seq., (the Act).
After notice to the parties, a hearing on the merits took place in Las Vegas, Nevada on November 27, 1984.
The citations, the standards allegedly violated and the proposed penalties therefor are as follows:
Citation No. 30 C.F.R. Proposed Penalty
2008000A 55.12-25 $225
2008000B 55.12-2 225
2008000C 55.12-40 225
2084002 55.12-65 420
2084003 55.12-1 420
The cited regulations provide as follows:
55.12-25 Mandatory. All metal enclosing or encasing electrical circuits shall be grounded or provided with equivalent protection. This requirement does not apply to battery-operated equipment.
~1922
55.12-2 Mandatory. Electric equipment and circuits shall be provided with switches or other controls. Such switches or controls shall be of approved design and construction and shall be properly installed.
55.12-40 Mandatory. Operating controls shall be installed so that they can be operated without danger of contact with energized conductors.
55.12-65 Mandatory. Powerlines, including trolley wires, and telephone circuits shall be protected against short circuits and lightning.
55.12-1 Mandatory. Circuits shall be protected against excessive overload by fuses or circuits breakers of the correct type and capacity.
The parties waived their right to file post-trial briefs.
Issues
The issues are what penalties are appropriate for the violations.
Stipulation
Samuel N. Rucker, President of respondent, admitted the company was in violation of the regulations. Further, the company was only contesting the amount of the penalties (Tr. 25-27).
Summary of the Evidence
Gary Ferrin, an MSHA inspector with extensive expertise in electricity, inspected Lava Products on September 15, 1983 (Tr. 6-10).
On that date the inspector issued five separate withdrawal orders and five separate citations under section 104 of the Act. He subsequently vacated the orders and citations and issued them under a single order (Tr. 28, 29).
There were three workers at the site. This was the average workforce (Tr. 29). When he returned to the site on September 20 he found three of the violative conditions had been abated. In his opinion, the condition of imminent danger no longer existed at the time of the later inspection (Tr. 30, 31).
The hazards here could cause death or serious injury to the three workers (Tr. 32). On his reinspection the entire plant had been grounded and the inspector terminated the violation of 55.12-25. The violations of 55.12-1 and 55.12-65 had not yet been abated (Tr. 33). Hazards of fire and a possible fatal shock could result from the violation of 55.12-65 (Tr. 39, 40).
~1923
Concerning the violation of 55.12-2 there were two service entrances on the switches. This required a person to open the door and strike the contact with a stick (Tr. 34). In addition, the citation for this violation was issued because the switch was upside down and thus not properly installed. If a person opened the reversed switch handle the fuse remained energized (Tr. 34, 36, 37).
The violation of 55.12-40, which had existed for two years, was a highly dangerous condition. The 480 volts could cause death or serious bodily injury (Tr. 35-38).
After granting two extensions to abate the inspector returned to the mine on January 4, 1984. The violations concerning 55.12-65 and 55.12-1 had not been abated. At that point the inspector issued a closure order against the entire electrical system (Tr. 41, 42). The violative conditions were, in fact, abated on January 13, 1984 (Tr. 42).
Samuel N. Rucker testified for Lava Products. The witness, part owner and manager of respondent, failed to rapidly abate all of the citations because he had difficulty in obtaining the services of an electrician (Tr. 47-49). St. George, Utah, with a population of 10,000, has only three electricians (Tr. 49, 50).
The owners of Lava Products have lost about $250,000 in the business. Mr. Rucker himself has not drawn any money from the company for 90 days (Tr. 51). The witness indicated the company had no funds and the proposed penalties might put the company into bankruptcy (Tr. 55).
Don Larkin, an accountant, owns seventy percent of the business. Larkin keeps the financial records and was aware of the hearing (Tr. 57, 58). The company had not filed for bankruptcy and the owners were attempting to sell it (Tr. 59).
Discussion
Respondent's admission of liability establishes the violations. All of the contested citations should be affirmed.
The Congressional directive to assess civil penalties is contained in Section 110(i), now 30 U.S.C. 820(i), of the Act. It provides as follows:
The Commission shall have authority to assess all civil penalties provided in this Act. In assessing civil monetary penalties, the Commission shall consider the operator's history of previous violations, the ap- ~1924 propriateness of such penalty to the size of the business of the operator charged, whether the operator was negligent, the effect on the operator's ability to continue in business, the gravity of the violation, and the demonstrated good faith of the person charged in attempting to achieve rapid compliance after notification of a violation.
In considering the above factors I note that the company has no adverse prior history. The size of respondent's business must be considered as small, inasmuch as it has only three employees. The operator was negligent in failing to correct the violative conditions. The evidence that the imposition of penalties may force the company into bankruptcy is rejected because such evidence was without any supporting financial statements. Particularly, I note that the majority stockholder, a public accountant, did not appear nor seek to offer any evidence on this subject. The gravity of each of these electrical violations should be considered as high. The company's good faith is apparent in abating the violations of 55.12-25, 55.12-2 and 55.12-40 within four days of the first inspection (Tr. 56). However, the company receives no credit for the violations of 55.12-65 and 55.12-1 because it did not rapidly abate these violations. On balance, I consider that the following penalties are appropriate:
Citation No. Penalty
2008000A $125
2008000B
125
2008000C
125
2084002
420
2084003
420
Conclusions of Law
Based on the entire record and the factual findings made in the narrative portions of this decision, the following conclusions of law are entered:
1. The Commission has jurisdiction to decide this case.
2. Respondent violated the citations herein and they should be affirmed and penalties for such violations should be assessed.
ORDER
Based on the foregoing facts and conclusions of law I enter the following order:
1. The following citations are affirmed and the civil penalties, as noted, are assessed:
~1925
Citation No. Penalty
2008000A $125
2008000B
125
2008000C
125
2084002
420
2084003
420
- Respondent is ordered to pay to the Secretary the sum of
$1,215 within 40 days of the date of this decision.John J. Morris Administrative Law Judge
What applies to your situation today?
This order bound one employer. Ezel checks the current MSHA standards and Commission precedent against your facts, with citations.
Opens in Ezel Pro.
- Checks the law as it stands today, not only this page
- Cites every source it relies on, so you can verify it
- Chat, drafting and research in one workspace