Riverside Cement Company (ALJ decision, January 14, 1981)

Riverside Cement Company (FMSHRC WEST 80-21-M): Stacker cable fitting citation upheld

Decision type
ALJ decision
Docket
WEST 80-21-M
Decided
January 14, 1981
Presiding judge
Outcome
Citations affirmed
Precedential status
Final order, not precedent
Checked against source
2026-10-22
Cited standards

Apply this to your situation

This order from 1981 bound only the parties to this case; it isn't precedent. Ask about your situation and see what the current MSHA standards and Commission precedent say, with citations.

Currency note: this decision dates from 1981
The MSHA standards may have been amended, penalty amounts have been adjusted, and later Commission or court decisions may have changed the analysis since then. Treat this page as historical context, not current compliance advice. Verify the current standard before relying on any specific rule, threshold, or penalty mentioned here.
Final ALJ decision, not Commission precedent
No later Commission review appears in the official index, so this ALJ decision became final under the 40-day rule in 30 U.S.C. § 823(d)(1). It binds the parties but is not Commission precedent. The full text below is from the official FMSHRC release.
About this page: The plain-English summary and decision snapshot below were written by Ezel based on the official FMSHRC release. The full text is the agency's own release.
Read the official release (fmshrc.gov)

Plain-English summary

MSHA cited Riverside Cement because an energized clinker stacker cable entered a junction box through its door rather than a proper fitting at the Crestmore Mine and Mill. Judge Paul Merlin found this arrangement violated the electrical cable standard. The inspector feared stacker movement might pull the cable against the door and damage it, creating a shock hazard. The judge found ordinary negligence but considered an accident somewhat remote because several things would have to go wrong before injury. He assessed a $150 penalty.

Decision snapshot

  • Cited standard: 30 C.F.R. § 57.12-8.
  • Outcome: Electrical cable fitting citation upheld; $150 civil penalty assessed.
  • Key point: Passing a cable through a junction box door did not satisfy the rule requiring proper fittings.

Full text (FMSHRC public release)

CCASE:
SOL (MSHA) v. RIVERSIDE CEMENT
DDATE:
19810114
TTEXT:
~240
Federal Mine Safety and Health Review Commission Office of Administrative Law Judges

SECRETARY OF LABOR,
Civil Penalty Proceeding
MINE SAFETY AND HEALTH
ADMINISTRATION (MSHA),
Docket No. WEST 80-21-M
PETITIONER A/O No. 04-00010-05015 V v.
Crestmore Mine and Mill
RIVERSIDE CEMENT COMPANY,
RESPONDENT

DECISION

Appearances: Theresa Kalinski, Esq., Office of the Solicitor, U.S.
Department of Labor, Los Angeles, California, for;
Petitioner, MSHA;
Jerry E. Hines, Esq., Gifford-Hill and Company, Dallas, Texas, for Respondent, Riverside Cement Company

Before: Judge Merlin

This case is a petition for the assessment of a civil penalty filed by the Government against Riverside Cement Company. A hearing was held on Tuesday, December 16, 1980.

The alleged violation was of 30 C.F.R. 57.12-8. Section 57.12-8 of the mandatory standards provides that:

Power wires and cables shall be insulated adequately where they pass into or out of electrical compartments.
Cables shall enter metal frames of motors, splice boxes, and electrical compartments only through proper fittings. When insulated wires, other than cables, pass through metal frames, the holes shall be substantially bushed with insulated bushings.

The citation, which was issued on May 14, 1979, set forth the following condition:

The trailing cable of the clinker stacker was not connected through proper fittings at the main junction box. The trailing cable was entered through the door of the junction box and the door fastened against the cable. The cable
~241 is energized and east belt was running. 440 v. Should a short circuit occur on the stacker electrical system which was energized it could be a fatal hazard to three employees who were cleaning the trailer walkway or other employees when attempting to mount the stacker.

At the hearing, the parties entered into the following stipulations (Tr. 2, 33):

(1) The operator is the owner and operator of the subject mine.

(2) The operator and the mine are subject to the jurisdiction of the Federal Mine Safety and Health Act of 1977.

(3) The administrative law judge has jurisdiction of this case.

(4) The inspector who issued the citation was a duly authorized representative of the Secretary.

(5) A true and correct copy of the subject citation was properly served upon the operator.

(6) Copies of the subject citation and termination of the violation in issue are authentic and may be admitted into evidence for the purposes of establishing their issuance, but not for the purpose of establishing the truthfulness or relevancy of any statements therein.

(7) The imposition of a penalty will not affect the operator's ability to continue in business.

(8) The alleged violation was abated in good faith.

(9) In overall terms, the operator has a moderate history of violations. In addition, the operator has a small history regarding this particular standard.

(10) The operator's size is large.

Testimony was given by the inspector who issued the citation and by the operator's safety engineer. The inspector testified that on the day of the inspection he observed the clinker stacker power cable attached inside the clinker stacker junction box and that the cable exited the box through the box's door (Tr. 10). He stated that this was not the way in which cables typically enter junction boxes since such cables normally enter junction boxes through proper fittings (Tr. 10). The cable itself was not winding and unwinding from a reel, as is usually the case (Tr. 25). Rather, the cable was laying on the ground following the stacker, and was tied to the stacker by a rope (Tr. 7-9). The inspector's concern was that the movement of the stacker could cause the rope to break, creating a situation where the weight of the cable would cause the edge or the door of the junction box to cut into ~242 the cable, creating a shock hazard (Tr. 12). The inspector testified that if the cable were cut and the ground and the fuses were not working properly the junction box and the stacker itself could become energized (Tr. 12-13). The inspector felt that if the cable had entered the junction box through insulated bushings then the likelihood of any damage to the cable would have been significantly lessened (Tr. 28). The safety engineer testified that a new reel for the cable was scheduled to be installed the next day (Tr. 32). The rope used to fasten the cable to the stacker circled the cable several times, preventing persons from pulling on the cable, which could break the connections inside the junction box (Tr. 30). He further testified to the type and quality of the cable (Tr. 30), and stated that there was both a grounding wire for the cable and a circuit breaker for the stacker, so that if a short were to occur the power would be cut off, regardless of how the cable was cut (Tr. 30-31).

I find that a violation of the mandatory standard occurred.

The regulation at issue here, 30 C.F.R. 57.12-8, requires that cables enter the metal frames of electrical compartments "only though proper fittings." Based upon the evidence I find that the way this cable entered the junction box did not constitute "proper fittings" and that therefore a violation occurred.

I further find the operator exhibited ordinary negligence because it should have known that this cable was not entering the junction box in the proper manner. Further, although any potential accident would be serious, the likelihood of an accident occurring is somewhat remote because of the chain of events that would have to occur before a person could be injured.

In light of the foregoing and taking into account all the statutory criteria a penalty of $150 is assessed.

ORDER

The operator is ORDERED to pay $150 within 30 days from the date of this decision.

Paul Merlin
Assistant Chief Administrative Law Judge